SECTION A: ANSWER ALL QUESTIONS
(1)
Thevenin’s theorem states that any linear, bilateral electrical network containing voltage sources and resistances can be replaced by an equivalent circuit consisting of a single voltage source in series with a single resistance, as viewed from the load terminals.
═══════════════════════════
(2)
To detect fire or smoke automatically and activate an alarm to warn occupants so that appropriate action can be taken to prevent injury and property damage.
═══════════════════════════
(3)

═══════════════════════════
(4)
(i) Indoor substation.
(ii) Outdoor substation.
═══════════════════════════
(5)
Static electricity is the accumulation of electric charges on the surface of an object, which remain at rest until discharged.
═══════════════════════════
(6)
Varnishing provides electrical insulation to the motor windings, prevents moisture absorption and protects the windings against dust, dirt and mechanical damage.
═══════════════════════════
(7)
Tap changers are necessary to adjust the transformer turns ratio and maintain the required output voltage when the input voltage or load conditions change.
═══════════════════════════
(8)
Luminous intensity is the amount of visible light emitted by a source in a particular direction per unit solid angle. Its SI unit is the candela (cd).
═══════════════════════════
(9)

═══════════════════════════
(10)
Newton’s third law states that for every action, there is an equal and opposite reaction.
═══════════════════════════
SECTION B: ANSWER FIVE(5) QUESTIONS ONLY
(11ai)
Electric shock: This occurs when a person comes into contact with exposed live conductors, damaged cables or faulty electrical equipment. It can cause severe burns, injury or death. To prevent electric shock, electrical installations should be properly insulated and earthed. Protective devices such as circuit breakers and residual current devices should also be installed.
(11aii)
Fire hazard: Faulty wiring, overloaded circuits, short circuits and loose connections can produce excessive heat or sparks. These may ignite combustible farm materials such as hay, straw, dry leaves and animal feed. Proper wiring, suitable protective devices, regular inspection and safe storage of combustible materials help to prevent electrical fires.
(11b)

How it works;
(i) Detection: Smoke or heat detectors sense smoke or an unusual rise in temperature.
(ii) Signal transmission: The detectors send a signal to the fire alarm control panel. A manual call point can also be activated by a person.
(iii) Alarm activation: The control panel activates the alarm bell or siren.
(iv) Warning: The alarm alerts occupants to the presence of fire.
(v) Evacuation: Occupants leave the building safely and the fire service is alerted.
═══════════════════════════
(12a)
(i) Provide oil collection pits beneath transformers to collect oil in case of leakage.
(ii) Construct oil-resistant concrete floors sloped towards the collection pit to prevent oil from spreading.
(iii) Provide retaining (bund) walls around the transformer to contain leaked oil.
(iv) Provide drainage channels and oil-water separators to separate oil from rainwater before disposal.
(12b)
A busbar is a thick metallic conductor, usually of copper or aluminium, used to collect electrical power from incoming circuits and distribute it to outgoing circuits, while an isolator is a mechanical switching device used to disconnect a circuit or equipment from the supply to provide safe isolation during maintenance.
A busbar carries and distributes electrical current, whereas an isolator provides a visible break in the circuit and is normally operated only when the circuit is not carrying load current.
═══════════════════════════
(14a)
Given: R = 10 Ω, L = 20 mH = 20 × 10⁻³ H, VL = 400 V, f = 50 Hz, three coils connected in delta.
For a delta connection:
Phase voltage, Vph = line voltage, VL = 400 V
Line current, IL = √3 × Iph
Inductive reactance of each coil:
XL = 2πfL
XL = 2 × 3.142 × 50 × 20 × 10⁻³
XL = 314.2 × 0.02
XL = 6.28 Ω
Impedance of each coil:
Z = √(R² + XL²)
Z = √(10² + 6.28²)
Z = √(100 + 39.44)
Z = √139.44
Z = 11.81 Ω
Phase current:
Iph = Vph/Z
Iph = 400/11.81
Iph = 33.87 A
(i) Line current:
IL = √3 × Iph
IL = 1.732 × 33.87
IL = 58.66 A, approximately 58.7 A
(ii) Total power consumed:
Power is used up only in the resistance of the three coils.
P = 3 × Iph² × R
P = 3 × (33.87)² × 10
P = 3 × 1147.2 × 10
P = 34,416 W
P = 34.42 kW
(14b)

═══════════════════════════
(15a)

(15b)
An interpole is a small auxiliary pole fitted between the main poles of a DC machine. Its purposes are:
(i) To improve commutation by neutralising the reactance voltage induced in the armature coil during commutation.
(ii) To prevent sparking at the brushes.
(iii) To maintain effective commutation under varying load conditions.
(iv) To reduce the effects of armature reaction in the commutation zone.
═══════════════════════════
(16a)

(16b)
Lissajous figures are patterns produced on the screen of a cathode-ray oscilloscope when two sinusoidal alternating signals are applied at the same time to the horizontal and vertical deflection inputs.
The horizontal signal moves the electron beam from side to side, while the vertical signal moves it up and down. The combined movements produce different patterns on the screen.
The shape of the figures depends on the frequency ratio and phase difference between the two signals. Equal frequencies may produce a straight line, an ellipse or a circle, depending on the phase difference, whereas different frequency ratios produce more complex patterns.
Lissajous figures are used to compare frequencies and determine the phase difference between two electrical signals.
═══════════════════════════
(17a)

(17b)
(i) Construction sites.
(ii) Agricultural installations.
(iii) Mining and quarrying installations.
(iv) Industrial installations.
(v) Temporary electrical installations.
(vi) Installations supplying portable electrical equipment where earth-fault protection is essential.
═══════════════════════════